Description of the wall construction
The monoblock element consists of two sheet steel shells, which are joined together over their entire surface using a rigid polyurethane foam core. The elements are joined together using a tongue and groove system.
Cladding and surface
Wall elements:
Coil-coated sheet steel with polyester coating, layer thickness 25 µm, delivered with PVC protective film, which is removed after completion of the construction work, all materials, except seals, in non-combustible design Color: various RAL of choice AG Connection profiles, frames, architraves, door leaves, etc.: High-quality corrosion-protected sheet metal. All visible surfaces powder-coated using a stoving process based on polyester and epoxy resins. Average coating thickness 80 µm, minimum 64 µm. The surface is completely smooth with a low gloss level, other coating techniques (fine structure, etc.) are possible. The surface is abrasion-resistant, easy to clean and resistant to repeated cleaning with commercially available disinfectants and cleaning agents and can withstand fumigation with hydrogen peroxide. All materials, except seals, in non-flammable finish Color: RAL of choice AG Due to different coating processes, color deviations may occur between wall elements and connecting profiles, frames, door frames, door leaves, etc.
Standard dimensions
Shell thickness
- Sheet thickness: 0.6 mm
Wall thickness
- 80 mm
- Special thicknesses are possible
Wall width
- Standard grid 1150 mm
Wall height
- limited by transportation and installation possibilities
Glazing
Solid wall
Double glazing with 2 x ESG 6 mm (toughened safety glass) Cut-outs for glazing are made on site. The cut edges are concealed with the inserted glass frames. The glass is glued flush into the inserted glass frames on both sides and permanently elastically grouted; the glazing can be easily replaced without removing the wall element.
Glass interior permanently dust- and fog-free, with all-round passe-partout in RAL color as desired.
All-glass wall
Single glazing 1 x ESG 12 mm (toughened safety glass)
Installation as a complete wall element. The glass panes are inserted in the middle and joined with permanently elastic joints; the glazing can be easily replaced without removing the wall element.
Media routing
Conditional installation of electrical cables is possible, as is the installation of switches, sockets and function switches.
Advantages
- Realization of high wall heights possible
The monoblock element consists of two sheet steel shells that are joined together over their entire surface using a polyurethane rigid foam core. The elements are joined together using a tongue and groove system.